Annistown Elementary Facility

53 Gwinnett Drive, Bldg E, Lawrenceville, GA 30046


About this Page

On this page you will be able to see results from this facility by tap as available. To help you understand these results, you can watch this video or read "Understanding the Results of Your Water Test" on pages 7-9 of our Full Program Instructions.

The Lead Concentration in Water shows the result from the sample the center collected. ppb means parts per billion, and is a way of explaining the amount of lead in water.

Centers and schools are able to post mitigation actions for each tap here following these instructions.


Taps and Results
  • 1.205
    Location: 1.205 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    4.97 ppbApril 16, 2024
  • 1.103a
    Location: Classroom: 1.103 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.28 ppbMarch 1, 2024
  • 1.104a
    Location: Classroom: 1.104 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.16 ppbFebruary 26, 2024
  • 1.107a
    Location: Classroom: 1.107 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.49 ppbFebruary 26, 2024
  • 1.126a
    Location: Classroom: 1.126 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.28 ppbFebruary 26, 2024
  • 1.126b
    Location: Classroom: 1.126 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.29 ppbFebruary 26, 2024
  • 1.147a
    Location: Classroom: 1.147 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.97 ppbFebruary 26, 2024
  • 1.171a
    Location: Classroom: 1.171 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    7.01 ppbFebruary 26, 2024
  • 1.173a
    Location: Classroom: 1.173 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.80 ppbFebruary 26, 2024
  • 1.173aB
    Location: Classroom: 1.173 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.77 ppbFebruary 26, 2024
  • 1.174a
    Location: Classroom: 1.174 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.61 ppbFebruary 26, 2024
  • 1.174aB
    Location: Classroom: 1.174 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    Facility indicated tap does not exist
  • 1.175aB
    Location: Classroom: 1.175 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.46 ppbFebruary 26, 2024
  • 1.175a
    Location: Classroom: 1.175 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.71 ppbFebruary 26, 2024
  • 1.179a
    Location: Classroom: 1.179 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.07 ppbFebruary 26, 2024
  • 1.179aB
    Location: Classroom: 1.179 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    2.50 ppbFebruary 26, 2024
  • 1.189aB
    Location: Classroom: 1.189 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.61 ppbFebruary 26, 2024
  • 1.189a
    Location: Classroom: 1.189 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.78 ppbFebruary 26, 2024
  • 1.202a
    Location: Classroom: 1.202 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.54 ppbFebruary 26, 2024
  • 1.205a
    Location: Classroom: 1.205 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    Sample not received, missing or not sampled
  • 1.207a
    Location: Classroom: 1.207 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.32 ppbFebruary 26, 2024
  • 1.207aB
    Location: Classroom: 1.207 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.31 ppbFebruary 26, 2024
  • 1.208aB
    Location: Classroom: 1.208 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.25 ppbFebruary 26, 2024
  • 1.208a
    Location: Classroom: 1.208 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.42 ppbFebruary 26, 2024
  • 1.209a
    Location: Classroom: 1.209 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.76 ppbFebruary 26, 2024
  • 1.209aB
    Location: Classroom: 1.209 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.25 ppbFebruary 26, 2024
  • 1.214a
    Location: Classroom: 1.214 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.27 ppbFebruary 26, 2024
  • 1.214aB
    Location: Classroom: 1.214 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.47 ppbFebruary 26, 2024
  • 3.101a
    Location: Classroom: 3.101 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.70 ppbFebruary 26, 2024
  • 3.101aB
    Location: Classroom: 3.101 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    86.12 ppb The reported value is from a dilutionMarch 1, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    Facility indicated water outlet removed
    Facility indicated water outlet removed
    Remediation Actions - recorded March 12, 2024
    Low-Cost Risk Mitigation Measures
    Removed faucet fixtures
  • 3.105a
    Location: Classroom: 3.105 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    6.87 ppbFebruary 26, 2024
  • 3.105aB
    Location: Classroom: 3.105 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    36.65 ppbMarch 1, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    Facility indicated water outlet removed
    Facility indicated water outlet removed
    Remediation Actions - recorded March 12, 2024
    Low-Cost Risk Mitigation Measures
    Removed faucet fixtures
  • 3.106a
    Location: Classroom: 3.106 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    5.29 ppbFebruary 26, 2024
  • 3.106aB
    Location: Classroom: 3.106 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.35 ppbFebruary 26, 2024
  • 3.107a
    Location: Classroom: 3.107 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.85 ppbFebruary 26, 2024
  • 3.107aB
    Location: Classroom: 3.107 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    833.86 ppb The reported value is from a dilutionMarch 1, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    Facility indicated water outlet removed
    Facility indicated water outlet removed
    Remediation Actions - recorded March 12, 2024
    Low-Cost Risk Mitigation Measures
    Removed faucet fixtures
  • 3.108a
    Location: Classroom: 3.108 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    2.45 ppbFebruary 26, 2024
  • 3.108aB
    Location: Classroom: 3.108 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    6.49 ppbFebruary 26, 2024
  • 3.113a
    Location: Classroom: 3.113 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    3.35 ppbFebruary 26, 2024
  • 3.113aB
    Location: Classroom: 3.113 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    10.19 ppbFebruary 28, 2024
    Remediation Actions - recorded November 1, 2024
    Low-Cost Risk Mitigation Measures
    Removed faucet fixtures
  • 3.119a
    Location: Classroom: 3.119 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.18 ppbFebruary 26, 2024
  • 3.121a
    Location: Classroom: 3.121 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.68 ppbFebruary 26, 2024
  • 3.123a
    Location: Classroom: 3.123 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    93.96 ppbFebruary 26, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    429.56 ppb The reported value is from a dilutionFirst DrawApril 10, 2024
    1.19 ppb30-second FlushApril 10, 2024
    Remediation Actions - recorded March 12, 2024
    Low-Cost Risk Mitigation Measures
    Replaced faucet fixtures
  • 3.123aB
    Location: Classroom: 3.123 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    49.67 ppbFebruary 26, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    Facility indicated water outlet removed
    Facility indicated water outlet removed
    Remediation Actions - recorded March 12, 2024
    Low-Cost Risk Mitigation Measures
    Removed faucet fixtures
  • 3.124a
    Location: Classroom: 3.124 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    5.52 ppbFebruary 26, 2024
  • 3.124aB
    Location: Classroom: 3.124 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.93 ppbFebruary 26, 2024
  • 3.129a
    Location: Classroom: 3.129 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.94 ppbFebruary 26, 2024
  • 3.129aB
    Location: Classroom: 3.129 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    56.78 ppbFebruary 26, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    Facility indicated water outlet removed
    Facility indicated water outlet removed
    Remediation Actions - recorded March 12, 2024
    Low-Cost Risk Mitigation Measures
    Removed faucet fixtures
  • 3.131a
    Location: Classroom: 3.131 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    2.97 ppbFebruary 26, 2024
  • 3.131aB
    Location: Classroom: 3.131 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    177.22 ppb The reported value is from a dilutionFebruary 28, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    Facility indicated water outlet removed
    Facility indicated water outlet removed
    Remediation Actions - recorded March 12, 2024
    Low-Cost Risk Mitigation Measures
    Removed faucet fixtures
  • 3.132a
    Location: Classroom: 3.132 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    4.00 ppbFebruary 26, 2024
  • 3.132aB
    Location: Classroom: 3.132 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    62.30 ppbFebruary 26, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    Facility indicated water outlet removed
    Facility indicated water outlet removed
    Remediation Actions - recorded March 12, 2024
    Low-Cost Risk Mitigation Measures
    Removed faucet fixtures
  • 3.133a
    Location: Classroom: 3.133 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    17.21 ppbFebruary 26, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    1.48 ppbFirst DrawApril 10, 2024
    0.21 ppb30-second FlushApril 10, 2024
    Remediation Actions - recorded March 12, 2024
    Low-Cost Risk Mitigation Measures
    Replaced faucet fixtures
  • 3.133aB
    Location: Classroom: 3.133 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    25.03 ppbFebruary 26, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    Facility indicated water outlet removed
    Facility indicated water outlet removed
    Remediation Actions - recorded March 12, 2024
    Low-Cost Risk Mitigation Measures
    Removed faucet fixtures
  • 1.121a
    Location: Kitchen/Cafeteria ⋅ 1.121
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.59 ppbFebruary 26, 2024
  • 1.113a
    Location: Kitchen/Cafeteria ⋅ 1.113
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.23 ppbFebruary 26, 2024
  • 1.113bPF
    Location: Kitchen/Cafeteria ⋅ 1.113
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    557.57 ppb The reported value is from a dilutionFebruary 28, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    0.14 ppbFirst DrawApril 10, 2024
    0.11 ppb30-second FlushApril 10, 2024
    Remediation Actions - recorded March 12, 2024
    Low-Cost Risk Mitigation Measures
    Replaced faucet fixtures
  • 1.113cPF
    Location: Kitchen/Cafeteria ⋅ 1.113
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    3.92 ppbFebruary 26, 2024
  • 1.139WFa
    Location: Water Fountains ⋅ 1.130
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.81 ppbFebruary 26, 2024
  • 1.139WFb
    Location: Water Fountains ⋅ 1.130
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.35 ppbFebruary 26, 2024
  • 1.141WFc
    Location: Water Fountains ⋅ 1.130
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.17 ppbFebruary 26, 2024
  • 1.141dBF
    Location: Water Fountains ⋅ 1.130
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.25 ppbFebruary 26, 2024
  • 1.111WFa
    Location: Water Fountains ⋅ 1.111
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.58 ppbFebruary 26, 2024
  • 1.185WFc
    Location: Water Fountains ⋅ 1.200
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.19 ppbFebruary 26, 2024
  • 1.185WFd
    Location: Water Fountains ⋅ 1.200
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.23 ppbFebruary 26, 2024
  • 1.185WFa
    Location: Water Fountains ⋅ 1.200
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.19 ppbFebruary 26, 2024
  • 1.185WFb
    Location: Water Fountains ⋅ 1.200
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.60 ppbFebruary 26, 2024
  • 3.122WFa
    Location: Water Fountains ⋅ 3.120
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.34 ppbFebruary 26, 2024
  • 3.122WFb
    Location: Water Fountains ⋅ 3.120
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.17 ppbFebruary 26, 2024