Shiloh Middle Facility

53 Gwinnett Drive, Bldg E, Lawrenceville, GA 30046


About this Page

On this page you will be able to see results from this facility by tap as available. To help you understand these results, you can watch this video or read "Understanding the Results of Your Water Test" on pages 7-9 of our Full Program Instructions.

The Lead Concentration in Water shows the result from the sample the center collected. ppb means parts per billion, and is a way of explaining the amount of lead in water.

Centers and schools are able to post mitigation actions for each tap here following these instructions.


Taps and Results
  • 1.126a
    Location: Classroom: 1.126 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    2.90 ppbJune 7, 2024
  • 1.132a
    Location: Classroom: 1.132 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    6.45 ppbJune 7, 2024
  • 1.160a
    Location: Classroom: 1.160 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.50 ppbJune 7, 2024
  • 1.170a
    Location: Classroom: 1.170 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    4.34 ppbJune 7, 2024
  • 1.192a
    Location: Classroom: 1.192 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.42 ppbJune 7, 2024
  • 1.192aB
    Location: Classroom: 1.192 ⋅ Sink S
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.78 ppbJune 7, 2024
  • 1.192b
    Location: Classroom: 1.192 ⋅ Sink S
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    18.99 ppbJune 7, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    984.83 ppbFirst DrawAugust 9, 2024
    30.87 ppb30-second FlushAugust 9, 2024
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    11.69 ppbSeptember 25, 2024
    Remediation Actions - recorded July 15, 2024
    Low-Cost Risk Mitigation Measures
    Replaced faucet fixtures
    Additional Risk Mitigation Measures
    Replaced other plumbing components
  • 1.192c
    Location: Classroom: 1.192 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    8.81 ppbJune 7, 2024
    Remediation Actions - recorded November 1, 2024
    Low-Cost Risk Mitigation Measures
    Replaced faucet fixtures
    Additional Risk Mitigation Measures
    Replaced other plumbing components
  • 1.192cB
    Location: Classroom: 1.192 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    6.69 ppbJune 7, 2024
  • 1.195a
    Location: Classroom: 1.195 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    229.43 ppb The reported value is from a dilutionJune 11, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    2,554.10 ppbFirst DrawAugust 9, 2024
    146.32 ppb30-second FlushAugust 9, 2024
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    39.74 ppbSeptember 25, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    Facility indicated duplicate entry
    Sample not received, missing or not sampled
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    37.26 ppbOctober 30, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    2.61 ppbFirst DrawJanuary 2, 2025
    2.09 ppb30-second FlushJanuary 2, 2025
    Remediation Actions - recorded July 15, 2024
    Low-Cost Risk Mitigation Measures
    Replaced faucet fixtures
    Additional Risk Mitigation Measures
    Replaced other plumbing components
  • 1.196a
    Location: Classroom: 1.196 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    300.82 ppb The reported value is from a dilutionJune 11, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    1,888.30 ppbFirst DrawAugust 12, 2024
    122.43 ppb30-second FlushAugust 9, 2024
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    8.74 ppbSeptember 25, 2024
    Remediation Actions - recorded July 15, 2024
    Low-Cost Risk Mitigation Measures
    Replaced faucet fixtures
    Additional Risk Mitigation Measures
    Replaced other plumbing components
  • 1.199a
    Location: Classroom: 1.199 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    11,381.82 ppb The reported value is from a dilutionJune 11, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    62.94 ppbFirst DrawAugust 9, 2024
    41.20 ppb30-second FlushAugust 9, 2024
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    8.53 ppbSeptember 25, 2024
    Remediation Actions - recorded July 15, 2024
    Low-Cost Risk Mitigation Measures
    Replaced faucet fixtures
    Additional Risk Mitigation Measures
    Replaced other plumbing components
  • 1.202a
    Location: Classroom: 1.202 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    60.07 ppbJune 7, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    370.25 ppbFirst DrawAugust 9, 2024
    5.71 ppb30-second FlushAugust 9, 2024
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    4.73 ppbSeptember 25, 2024
    Remediation Actions - recorded July 15, 2024
    Low-Cost Risk Mitigation Measures
    Replaced faucet fixtures
    Additional Risk Mitigation Measures
    Replaced other plumbing components
  • 2.108a
    Location: Classroom: 2.108 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.83 ppbJune 7, 2024
  • 2.108b
    Location: Classroom: 2.108 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    3.34 ppbJune 7, 2024
  • 2.108c
    Location: Classroom: 2.108 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    2.73 ppbJune 7, 2024
  • 3.116a
    Location: Classroom: 3.116 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.70 ppbJune 7, 2024
  • 3.116b
    Location: Classroom: 3.116 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    3.81 ppbJune 7, 2024
  • 3.117a
    Location: Classroom: 3.117 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    2.86 ppbJune 7, 2024
  • 3.117b
    Location: Classroom: 3.117 ⋅ Sink Bubbler
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.86 ppbJune 7, 2024
  • 3.119a
    Location: Classroom: 3.119 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.93 ppbJune 7, 2024
  • 4.151a
    Location: Classroom: 4.151 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.30 ppbJune 7, 2024
  • 4.162a
    Location: Classroom: 4.162 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.58 ppbJune 7, 2024
  • 1.222a - Prep Sink
    Location: Kitchen/Cafeteria ⋅ 1.222
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.81 ppbJune 7, 2024
  • 1.222b - Prep Sink
    Location: Kitchen/Cafeteria ⋅ 1.222
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbJune 7, 2024
  • 1.222c - Prep Sink
    Location: Kitchen/Cafeteria ⋅ 1.222
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.60 ppbJune 7, 2024
  • 1.222PFa - Sink
    Location: Kitchen/Cafeteria ⋅ 1.222
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.78 ppbJune 7, 2024
  • 1.222PFb - Small Kettle
    Location: Kitchen/Cafeteria ⋅ 1.222
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.63 ppbJune 7, 2024
  • 1.222PFc - Large Kettle
    Location: Kitchen/Cafeteria ⋅ 1.222
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.34 ppbJune 7, 2024
  • 1.222KSd - Prep Sink
    Location: Kitchen/Cafeteria ⋅ 1.222
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.38 ppbJune 7, 2024
  • 1.222SFb - UCM
    Location: Kitchen/Cafeteria ⋅ 1.222
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    4.40 ppbJune 7, 2024
  • 4.124WFa
    Location: Water Fountains ⋅ 4.101
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbJune 6, 2024
  • 4.118WFa
    Location: Water Fountains ⋅ 4.101
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbJune 7, 2024
  • 4.140WFa
    Location: Water Fountains ⋅ 4.133
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbJune 7, 2024
  • 4.158BFa
    Location: Water Fountains ⋅ 4.100
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbJune 7, 2024
  • 4.158WFa
    Location: Water Fountains ⋅ 4.100
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbJune 7, 2024
  • 1.116WFa
    Location: Water Fountains ⋅ 1.108
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.34 ppbJune 7, 2024
  • 1.116WFb
    Location: Water Fountains ⋅ 1.108
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.43 ppbJune 7, 2024
  • 1.146WFa
    Location: Water Fountains ⋅ 1.151
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.44 ppbJune 7, 2024
  • 1.146WFb
    Location: Water Fountains ⋅ 1.151
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    2.37 ppbJune 7, 2024
  • 1.129WFa
    Location: Water Fountains ⋅ 1.136
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.43 ppbJune 7, 2024
  • 1.190WFa
    Location: Water Fountains ⋅ 1.182
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.28 ppbJune 7, 2024
  • 1.221WFa
    Location: Water Fountains ⋅ 1.110
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbJune 7, 2024
  • 1.240WFa
    Location: Water Fountains ⋅ 1.240
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.10 ppbJune 7, 2024
  • 1.240WFb
    Location: Water Fountains ⋅ 1.240
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.10 ppbJune 7, 2024
  • 1.243WFa
    Location: Water Fountains ⋅ 1.243
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.16 ppbJune 7, 2024
  • 1.243WFb
    Location: Water Fountains ⋅ 1.243
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.21 ppbJune 7, 2024
  • 1.232BFa
    Location: Water Fountains ⋅ 1.100
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.53 ppbJune 7, 2024
  • 2.111WFa
    Location: Water Fountains ⋅ 2.122
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.03 ppbJune 7, 2024
  • 2.111WFb
    Location: Water Fountains ⋅ 2.122
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.19 ppbJune 7, 2024
  • 3.128WFa
    Location: Water Fountains ⋅ 3.130
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbJune 7, 2024
  • 3.101WFa
    Location: Water Fountains ⋅ 3.100
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.17 ppbJune 7, 2024
  • 5.111AWFa
    Location: Water Fountains ⋅ 5.100
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbJune 7, 2024
  • 5.111AWFb
    Location: Water Fountains ⋅ 5.100
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.14 ppbJune 7, 2024
  • 5.211WFa
    Location: Water Fountains ⋅ 5.200
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.11 ppbJune 7, 2024
  • 5.211WFb
    Location: Water Fountains ⋅ 5.200
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbJune 6, 2024