1.012WFbBF
Location: Classroom: 1.012 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 20, 2024 |
-
1.055aF
Location: Classroom: 1.055 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.49 ppb | March 19, 2024 |
-
1.056aF
Location: Classroom: 1.056 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
68.87 ppb | March 21, 2024 |
Followup Lead Concentration in Water (from RTI International)
Value |
Sample Type |
Analysis Date |
0.26 ppb | First Draw | May 7, 2024 |
< 0.10 ppb | 30-second Flush | May 7, 2024 |
Remediation Actions - recorded April 8, 2024
Low-Cost Risk Mitigation Measures
Replaced faucet fixtures
-
1.067aB
Location: Classroom: 1.067 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.91 ppb | March 19, 2024 |
-
1.067aGN
Location: Classroom: 1.067 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.11 ppb | March 19, 2024 |
-
1.070aB
Location: Classroom: 1.070 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
3.10 ppb | March 19, 2024 |
-
1.070aGN
Location: Classroom: 1.070 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.98 ppb | March 19, 2024 |
-
1.071aB
Location: Classroom: 1.072 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.67 ppb | March 19, 2024 |
-
1.071aGN
Location: Classroom: 1.072 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.28 ppb | March 19, 2024 |
-
1.073aB
Location: Classroom: 1.073 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.82 ppb | March 19, 2024 |
-
1.073aGN
Location: Classroom: 1.073 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.53 ppb | March 19, 2024 |
-
1.077aB
Location: Classroom: 1.077 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
Sample not received, missing or not sampled |
-
1.077aGN
Location: Classroom: 1.077 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.50 ppb | March 19, 2024 |
-
1.077aB
Location: Classroom: 1.077 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.19 ppb | March 19, 2024 |
-
1.077aGN
Location: Classroom: 1.077 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
Sample not received, missing or not sampled |
-
1.079aB
Location: Classroom: 1.079 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 20, 2024 |
-
1.079aGN
Location: Classroom: 1.079 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.12 ppb | March 20, 2024 |
-
1.082aB
Location: Classroom: 1.082 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.73 ppb | March 20, 2024 |
-
1.082aGN
Location: Classroom: 1.082 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
3.25 ppb | March 20, 2024 |
-
1.083aB
Location: Classroom: 1.083 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
8.66 ppb | March 20, 2024 |
Remediation Actions - recorded October 3, 2024
Low-Cost Risk Mitigation Measures
Removed faucet fixtures
-
1.083aGN
Location: Classroom: 1.083 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.10 ppb | March 20, 2024 |
-
1.085aB
Location: Classroom: 1.085 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
3.08 ppb | March 20, 2024 |
-
1.085aGN
Location: Classroom: 1.085 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
9.17 ppb | March 20, 2024 |
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.61 ppb | October 16, 2024 |
Remediation Actions - recorded November 8, 2024
Low-Cost Risk Mitigation Measures
Replaced faucet fixtures
Additional Risk Mitigation Measures
Replaced other plumbing components
-
1.086aB
Location: Classroom: 1.086 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
Sample not received, missing or not sampled |
-
1.086aGN
Location: Classroom: 1.086 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.48 ppb | March 20, 2024 |
-
1.086aB
Location: Classroom: 1.086 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.82 ppb | March 20, 2024 |
-
1.088aB
Location: Classroom: 1.088 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.01 ppb | March 20, 2024 |
-
1.088aGN
Location: Classroom: 1.088 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.45 ppb | March 20, 2024 |
-
1.096aB
Location: Classroom: 1.096 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.78 ppb | March 20, 2024 |
-
1.096aGN
Location: Classroom: 1.096 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.27 ppb | March 20, 2024 |
-
1.098aB
Location: Classroom: 1.098 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.14 ppb | March 20, 2024 |
-
1.098aGN
Location: Classroom: 1.098 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.71 ppb | March 20, 2024 |
-
1.100aB
Location: Classroom: 1.100 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.50 ppb | March 20, 2024 |
-
1.100aGN
Location: Classroom: 1.100 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.30 ppb | March 20, 2024 |
-
1.102aB
Location: Classroom: 1.102 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.74 ppb | March 20, 2024 |
-
1.102aGN
Location: Classroom: 1.102 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.90 ppb | March 20, 2024 |
-
1.104aB
Location: Classroom: 1.104 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.96 ppb | March 20, 2024 |
-
1.104aGN
Location: Classroom: 1.104 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.24 ppb | March 20, 2024 |
-
1.105aB
Location: Classroom: 1.105 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.94 ppb | March 20, 2024 |
-
1.105aGN
Location: Classroom: 1.105 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.08 ppb | March 20, 2024 |
-
1.107aB
Location: Classroom: 1.107 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.12 ppb | March 20, 2024 |
-
1.107aGN
Location: Classroom: 1.107 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.31 ppb | March 20, 2024 |
-
1.108aGN
Location: Classroom: 1.108 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.15 ppb | March 20, 2024 |
-
1.108aB
Location: Classroom: 1.108 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.63 ppb | March 20, 2024 |
-
1.109GN
Location: Classroom: 1.109 ⋅ Sink Faucet / Clinic
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
5.44 ppb | March 20, 2024 |
-
1.112aB
Location: Classroom: 1.112 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.44 ppb | March 20, 2024 |
-
1.112aGN
Location: Classroom: 1.112 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.17 ppb | March 20, 2024 |
-
1.113aB
Location: Classroom: 1.113 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.36 ppb | March 20, 2024 |
-
1.113aGN
Location: Classroom: 1.113 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
3.10 ppb | March 20, 2024 |
-
1.115aB
Location: Classroom: 1.115 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.51 ppb | March 20, 2024 |
-
1.115aGN
Location: Classroom: 1.115 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.07 ppb | March 19, 2024 |
-
1.117aB
Location: Classroom: 1.117 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.37 ppb | March 19, 2024 |
-
1.117aGN
Location: Classroom: 1.117 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.79 ppb | March 19, 2024 |
-
1.095WFfB
Location: Classroom: 1.118 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.10 ppb | March 19, 2024 |
-
1.119aB
Location: Classroom: 1.119 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.53 ppb | March 19, 2024 |
-
1.119aGN
Location: Classroom: 1.119 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.90 ppb | March 19, 2024 |
-
1.120aB
Location: Classroom: 1.120 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
6.58 ppb | March 19, 2024 |
-
1.120aGN
Location: Classroom: 1.120 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
7.26 ppb | March 21, 2024 |
-
1.121aB
Location: Classroom: 1.121 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.70 ppb | March 19, 2024 |
-
1.121aGN
Location: Classroom: 1.121 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.49 ppb | March 19, 2024 |
-
1.123aB
Location: Classroom: 1.123 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.38 ppb | March 19, 2024 |
-
1.123aGN
Location: Classroom: 1.123 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.95 ppb | March 19, 2024 |
-
1.124aB
Location: Classroom: 1.124 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.72 ppb | March 19, 2024 |
-
1.124aGN
Location: Classroom: 1.124 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.80 ppb | March 19, 2024 |
-
1.125aB
Location: Classroom: 1.125 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.19 ppb | March 19, 2024 |
-
1.125aGN
Location: Classroom: 1.125 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.46 ppb | March 19, 2024 |
-
1.127aB
Location: Classroom: 1.127 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.44 ppb | March 19, 2024 |
-
1.127aGN
Location: Classroom: 1.127 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.75 ppb | March 19, 2024 |
-
1.129aB
Location: Classroom: 1.129 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.18 ppb | March 20, 2024 |
-
1.129aGN
Location: Classroom: 1.129 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.59 ppb | March 20, 2024 |
-
1.130aB
Location: Classroom: 1.130 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.70 ppb | March 20, 2024 |
-
1.130aGN
Location: Classroom: 1.130 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
3.67 ppb | March 20, 2024 |
-
1.131aGN
Location: Classroom: 1.131 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.38 ppb | March 20, 2024 |
-
1.131aB
Location: Classroom: 1.131 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
5.79 ppb | March 20, 2024 |
-
1.131aGN
Location: Classroom: 1.131 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
Sample not received, missing or not sampled |
-
1.161aF
Location: Classroom: 1.161 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
54.26 ppb | March 19, 2024 |
Followup Lead Concentration in Water (from RTI International)
Value |
Sample Type |
Analysis Date |
0.64 ppb | First Draw | May 7, 2024 |
0.12 ppb | 30-second Flush | May 6, 2024 |
Remediation Actions - recorded April 8, 2024
Low-Cost Risk Mitigation Measures
Replaced faucet fixtures
-
1.161bF
Location: Classroom: 1.161 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
17.70 ppb | March 19, 2024 |
Followup Lead Concentration in Water (from RTI International)
Value |
Sample Type |
Analysis Date |
0.21 ppb | First Draw | May 6, 2024 |
0.13 ppb | 30-second Flush | May 7, 2024 |
Remediation Actions - recorded April 8, 2024
Low-Cost Risk Mitigation Measures
Replaced faucet fixtures
-
1.164aF
Location: Classroom: 1.164 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
175.12 ppb The reported value is from a dilution | March 20, 2024 |
Followup Lead Concentration in Water (from RTI International)
Value |
Sample Type |
Analysis Date |
0.26 ppb | First Draw | May 7, 2024 |
0.11 ppb | 30-second Flush | May 7, 2024 |
Remediation Actions - recorded April 8, 2024
Low-Cost Risk Mitigation Measures
Replaced faucet fixtures
-
1.164bF
Location: Classroom: 1.164 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
64.14 ppb | March 20, 2024 |
Followup Lead Concentration in Water (from RTI International)
Value |
Sample Type |
Analysis Date |
0.49 ppb | First Draw | May 7, 2024 |
0.14 ppb | 30-second Flush | May 7, 2024 |
Remediation Actions - recorded April 8, 2024
Low-Cost Risk Mitigation Measures
Replaced faucet fixtures
-
3.067aB
Location: Classroom: 3.067 ⋅ Sink Bubbler
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
Sample not received, missing or not sampled |
-
3.067aGN
Location: Classroom: 3.067 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
Sample not received, missing or not sampled |
-
3.101aGN
Location: Classroom: 3.101 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.42 ppb | March 20, 2024 |
-
3.102aF
Location: Classroom: 3.102 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.19 ppb | March 20, 2024 |
-
3.106aGN
Location: Classroom: 3.106 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.39 ppb | March 20, 2024 |
-
3.109aF
Location: Classroom: 3.109 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 20, 2024 |
-
3.110aF
Location: Classroom: 3.110 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.89 ppb | March 20, 2024 |
-
3.112aGN
Location: Classroom: 3.112 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.13 ppb | March 20, 2024 |
-
3.116aGN
Location: Classroom: 3.116 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
4.95 ppb | March 20, 2024 |
-
3.117aGN
Location: Classroom: 3.117 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.46 ppb | March 20, 2024 |
-
3.118aGN
Location: Classroom: 3.118 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
3.34 ppb | March 20, 2024 |
-
3.124aGN
Location: Classroom: 3.124 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.86 ppb | March 19, 2024 |
-
3.131aGN
Location: Classroom: 3.131 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.16 ppb | March 19, 2024 |
-
3.132aF
Location: Classroom: 3.132 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.24 ppb | March 19, 2024 |
-
3.139aGN
Location: Classroom: 3.139 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.33 ppb | March 19, 2024 |
-
3.141aGN
Location: Classroom: 3.141 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.20 ppb | March 19, 2024 |
-
3.142aGN
Location: Classroom: 3.142 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 19, 2024 |
-
3.143aGN
Location: Classroom: 3.143 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.16 ppb | March 20, 2024 |
-
3.144aGN
Location: Classroom: 3.144 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.13 ppb | March 20, 2024 |
-
3.145aGN
Location: Classroom: 3.145 ⋅ Sink Faucet
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.02 ppb | March 19, 2024 |
-
1.005KSaGN
Location: Kitchen/Cafeteria ⋅ 1.005
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.72 ppb | March 19, 2024 |
-
1.005PFa(vcm)
Location: Kitchen/Cafeteria ⋅ 1.005
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
2.41 ppb | March 19, 2024 |
-
1.005PFb
Location: Kitchen/Cafeteria ⋅ 1.005
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
1.77 ppb | March 19, 2024 |
-
1.005PFc(vcm)
Location: Kitchen/Cafeteria ⋅ 1.005
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
23.23 ppb | March 19, 2024 |
Followup Lead Concentration in Water (from RTI International)
Value |
Sample Type |
Analysis Date |
1.70 ppb | First Draw | May 7, 2024 |
0.25 ppb | 30-second Flush | May 7, 2024 |
Remediation Actions - recorded April 8, 2024
Low-Cost Risk Mitigation Measures
Replaced faucet fixtures
-
1.005Fd
Location: Kitchen/Cafeteria ⋅ 1.005
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.17 ppb | March 19, 2024 |
-
1.095WFaB
Location: Water Fountains ⋅ 1.118
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 20, 2024 |
-
1.095WFbB
Location: Water Fountains ⋅ 1.118
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.14 ppb | March 20, 2024 |
-
1.095WFcB
Location: Water Fountains ⋅ 1.118
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 20, 2024 |
-
1.095WFdB
Location: Water Fountains ⋅ 1.118
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
0.11 ppb | March 20, 2024 |
-
1.095WFeB
Location: Water Fountains ⋅ 1.118
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 20, 2024 |
-
1.095WFfB
Location: Water Fountains ⋅ 1.118
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 19, 2024 |
-
1.013BFaB
Location: Water Fountains ⋅ 1.064
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 19, 2024 |
-
1.013WFbB
Location: Water Fountains ⋅ 1.064
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 20, 2024 |
-
1.013WFcB
Location: Water Fountains ⋅ 1.064
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 19, 2024 |
-
1.012WFaB
Location: Water Fountains ⋅ 1.064
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 19, 2024 |
-
1.012WFbB
Location: Water Fountains ⋅ 1.064
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 19, 2024 |
-
1.137WFaB
Location: Water Fountains ⋅ 1.118
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 19, 2024 |
-
1.137WFbB
Location: Water Fountains ⋅ 1.118
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 19, 2024 |
-
1.137WFcB
Location: Water Fountains ⋅ 1.118
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 20, 2024 |
-
1.137WFdB
Location: Water Fountains ⋅ 1.118
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 20, 2024 |
-
1.137WFeB
Location: Water Fountains ⋅ 1.118
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 20, 2024 |
-
1.137WFfB
Location: Water Fountains ⋅ 1.118
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
Sample not received, missing or not sampled |
-
3.126WFaB
Location: Water Fountains ⋅ 3.100
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 20, 2024 |
-
3.126WFbB
Location: Water Fountains ⋅ 3.100
Lead Concentration in Water (from RTI International)
Value |
Analysis Date |
< 0.10 ppb | March 20, 2024 |