Taps and Results
  • 1.103a
    Location: Classroom: 1.103 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    4.81 ppbApril 27, 2024
  • 1.104a
    Location: Classroom: 1.104 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.92 ppbApril 27, 2024
  • 1.105a
    Location: Classroom: 1.105 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.31 ppbApril 27, 2024
  • 1.106a
    Location: Classroom: 1.106 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.24 ppbApril 27, 2024
  • 1.108ca
    Location: Classroom: 1.108c ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.18 ppbApril 27, 2024
  • 1.109a
    Location: Classroom: 1.109 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.82 ppbApril 27, 2024
  • 1.111a
    Location: Classroom: 1.111 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    2.15 ppbApril 27, 2024
  • 1.117a
    Location: Classroom: 1.117 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.85 ppbApril 27, 2024
  • 1.121a
    Location: Classroom: 1.121 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.24 ppbApril 27, 2024
  • 1.122a
    Location: Classroom: 1.122 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.14 ppbApril 27, 2024
  • 1.123a
    Location: Classroom: 1.123 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.77 ppbApril 27, 2024
  • 1.126a
    Location: Classroom: 1.126 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.36 ppbApril 27, 2024
  • 1.128a
    Location: Classroom: 1.128 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.30 ppbApril 27, 2024
  • 1.132a
    Location: Classroom: 1.132 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.44 ppbApril 27, 2024
  • 1.135a
    Location: Classroom: 1.135 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.12 ppbApril 27, 2024
  • 1.137a
    Location: Classroom: 1.137 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 27, 2024
  • 1.139a
    Location: Classroom: 1.139 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.18 ppbApril 27, 2024
  • 1.141a
    Location: Classroom: 1.141 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.18 ppbApril 27, 2024
  • 1.143a
    Location: Classroom: 1.143 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.18 ppbApril 29, 2024
  • 1.145a
    Location: Classroom: 1.145 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.16 ppbApril 29, 2024
  • 1.151a
    Location: Classroom: 1.151 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.65 ppbApril 29, 2024
  • 1.157a
    Location: Classroom: 1.157 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.25 ppbApril 29, 2024
  • 1.159a
    Location: Classroom: 1.159 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.32 ppbApril 29, 2024
  • 1.161a
    Location: Classroom: 1.161 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.26 ppbApril 29, 2024
  • 1.163a
    Location: Classroom: 1.163 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.17 ppbApril 29, 2024
  • 1.165a
    Location: Classroom: 1.165 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.19 ppbApril 29, 2024
  • 1.167a
    Location: Classroom: 1.167 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.20 ppbApril 29, 2024
  • 1.169a
    Location: Classroom: 1.169 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.47 ppbApril 29, 2024
  • 1.173a
    Location: Classroom: 1.173 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.29 ppbApril 29, 2024
  • 1.177a
    Location: Classroom: 1.177 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.39 ppbApril 29, 2024
  • 1.179a
    Location: Classroom: 1.179 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.23 ppbApril 29, 2024
  • 1.181a
    Location: Classroom: 1.181 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.41 ppbApril 29, 2024
  • 1.183a
    Location: Classroom: 1.183 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.32 ppbApril 29, 2024
  • 1.184a
    Location: Classroom: 1.184 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    57.99 ppbApril 29, 2024
    Followup Lead Concentration in Water (from RTI International)
    Value Sample Type Analysis Date
    61.78 ppbFirst DrawJune 29, 2024
    0.37 ppb30-second FlushJune 29, 2024
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbSeptember 12, 2024
    Remediation Actions - recorded May 24, 2024
    Low-Cost Risk Mitigation Measures
    Replaced faucet fixtures
    Additional Risk Mitigation Measures
    Replaced other plumbing components
  • 1.186a
    Location: Classroom: 1.186 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.35 ppbApril 29, 2024
  • 1.196a
    Location: Classroom: 1.196 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.71 ppbApril 29, 2024
  • 1.206a
    Location: Classroom: 1.206 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.74 ppbApril 29, 2024
  • 1.207a
    Location: Classroom: 1.207 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.21 ppbApril 29, 2024
  • 1.208a
    Location: Classroom: 1.208 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    6.76 ppbApril 29, 2024
  • 1.209a
    Location: Classroom: 1.209 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.40 ppbApril 29, 2024
  • 1.211a
    Location: Classroom: 1.211 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    2.15 ppbApril 29, 2024
  • 1.212a
    Location: Classroom: 1.212 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.18 ppbApril 29, 2024
  • 1.213a
    Location: Classroom: 1.213 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    2.22 ppbApril 29, 2024
  • 1.214a
    Location: Classroom: 1.214 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    5.05 ppbApril 29, 2024
  • 1.216a
    Location: Classroom: 1.216 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.25 ppbApril 29, 2024
  • 1.217a
    Location: Classroom: 1.217 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    3.54 ppbApril 29, 2024
  • 1.218a
    Location: Classroom: 1.218 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.39 ppbApril 29, 2024
  • 1.219a
    Location: Classroom: 1.219 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.84 ppbApril 29, 2024
  • 1.221a
    Location: Classroom: 1.221 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.96 ppbApril 29, 2024
  • 1.222a
    Location: Classroom: 1.222 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.93 ppbApril 29, 2024
  • 1.223a
    Location: Classroom: 1.223 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.74 ppbApril 29, 2024
  • 1.239a
    Location: Classroom: 1.239 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 29, 2024
  • 1.239b
    Location: Classroom: 1.239 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.61 ppbApril 29, 2024
  • 1.242a
    Location: Classroom: 1.242 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    2.22 ppbApril 29, 2024
  • 1.242b
    Location: Classroom: 1.242 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.65 ppbApril 29, 2024
  • 1.248a
    Location: Classroom: 1.248 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.22 ppbApril 29, 2024
  • 1.258a
    Location: Classroom: 1.258 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.25 ppbApril 29, 2024
  • 2.112a
    Location: Classroom: 2.112 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.34 ppbApril 29, 2024
  • 2.116a
    Location: Classroom: 2.116 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.49 ppbApril 29, 2024
  • 2.117a
    Location: Classroom: 2.117 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.55 ppbApril 29, 2024
  • 2.118a
    Location: Classroom: 2.118 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.27 ppbApril 29, 2024
  • 2.119a
    Location: Classroom: 2.119 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.16 ppbApril 29, 2024
  • 2.124a
    Location: Classroom: 2.124 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.18 ppbApril 29, 2024
  • 2.210a
    Location: Classroom: 2.210 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.18 ppbApril 29, 2024
  • 2.211a
    Location: Classroom: 2.211 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.13 ppbApril 29, 2024
  • 2.213a
    Location: Classroom: 2.213 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.24 ppbApril 29, 2024
  • 2.216a
    Location: Classroom: 2.216 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.38 ppbApril 29, 2024
  • 2.221a
    Location: Classroom: 2.221 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.12 ppbApril 29, 2024
  • 2.223a
    Location: Classroom: 2.223 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.14 ppbApril 29, 2024
  • 2.224a
    Location: Classroom: 2.224 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.45 ppbApril 29, 2024
  • 2.226a
    Location: Classroom: 2.226 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.24 ppbApril 29, 2024
  • 2.227a
    Location: Classroom: 2.227 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.20 ppbApril 29, 2024
  • 2.228a
    Location: Classroom: 2.228 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.94 ppbApril 29, 2024
  • 2.229a
    Location: Classroom: 2.229 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.24 ppbApril 29, 2024
  • 2.230a
    Location: Classroom: 2.230 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 29, 2024
  • 2.231a
    Location: Classroom: 2.231 ⋅ Sink Faucet
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    3.07 ppbApril 29, 2024
  • 1.228a
    Location: Kitchen/Cafeteria ⋅ 1.228
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 29, 2024
  • 1.228b
    Location: Kitchen/Cafeteria ⋅ 1.228
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.21 ppbApril 29, 2024
  • 1.228c
    Location: Kitchen/Cafeteria ⋅ 1.228
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.58 ppbApril 29, 2024
  • 1.239a
    Location: Water Fountains ⋅ 1.240
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 27, 2024
  • 1.239b
    Location: Water Fountains ⋅ 1.240
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 27, 2024
  • 1.239c
    Location: Water Fountains ⋅ 1.240
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 27, 2024
  • 1.239d
    Location: Water Fountains ⋅ 1.240
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 29, 2024
  • 1.224a
    Location: Water Fountains ⋅ 1.224
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 29, 2024
  • 1.224b
    Location: Water Fountains ⋅ 1.224
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 29, 2024
  • 1.256a
    Location: Water Fountains ⋅ 1.250
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 29, 2024
  • 1.111a
    Location: Water Fountains ⋅ 1.110
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.37 ppbApril 29, 2024
  • 1.111b
    Location: Water Fountains ⋅ 1.110
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.45 ppbApril 29, 2024
  • 1.111c
    Location: Water Fountains ⋅ 1.110
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    0.35 ppbApril 29, 2024
  • 1.131a
    Location: Water Fountains ⋅ 1.130
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 27, 2024
  • 1.131b
    Location: Water Fountains ⋅ 1.130
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 29, 2024
  • 1.131c
    Location: Water Fountains ⋅ 1.130
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 29, 2024
  • 1.131d
    Location: Water Fountains ⋅ 1.130
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 29, 2024
  • 1.174a
    Location: Water Fountains ⋅ 1.180
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 27, 2024
  • 1.174b
    Location: Water Fountains ⋅ 1.180
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 27, 2024
  • 1.174c
    Location: Water Fountains ⋅ 1.180
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 27, 2024
  • 1.174d
    Location: Water Fountains ⋅ 1.180
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 27, 2024
  • 2.123a
    Location: Water Fountains ⋅ 2.120
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 27, 2024
  • 2.123b
    Location: Water Fountains ⋅ 2.120
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 27, 2024
  • 2.102a
    Location: Water Fountains ⋅ 2.105
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 27, 2024
  • 2.102b
    Location: Water Fountains ⋅ 2.105
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 27, 2024
  • 2.214a
    Location: Water Fountains ⋅ 2.215
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    1.27 ppbApril 27, 2024
  • 2.206a
    Location: Water Fountains ⋅ 2.205
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 27, 2024
  • 2.206b
    Location: Water Fountains ⋅ 2.205
    Lead Concentration in Water (from RTI International)
    Value Analysis Date
    < 0.10 ppbApril 29, 2024